This is a French day-shift handover note for Quellmoor Ridge Wind Farm dated 18/07/2026. It records turbine maintenance and status observations for WTG-09, WTG-07, WTG-04, and WTG-12, plus a follow-up action for the next team.
Key facts
- The note is for Quellmoor Ridge Wind Farm and was written by Élise Ternaux, wind turbine technician.1
- WTG-09 had its generator brushes replaced under work order WO-26-0436 following alarm A3210 from 16/07.2
- For WTG-09, the shortest measured brush was B3 at 16 mm, below the 18 mm threshold in WI-GEN-014.2
- For WTG-09, a complete LWS-P-51207 set was replaced and the brush-holder screws were tightened to 12 N·m.2
- WTG-09 was put through run-in at 50 % power for 8 hours, until 20:00 that evening.2
- WTG-07 reached a maximum oil temperature of 66 °C that day, had no alarm, and still had high vibration while awaiting the bearing.2
- WTG-04 received a ground-based visual inspection of blade B, with nothing new noted.2
- WTG-12 had its anti-pollution kit restocked.2
- The next team was asked to check the end of the WTG-09 run-in at 20:00 and return it to 100 % power.3
Contents
Header
The note is marked fictional and not for operational use; it is a day-shift handover note dated 18/07/2026.4 It was written by Élise Ternaux, wind turbine technician, for Quellmoor Ridge Wind Farm.4
Shift work and turbine status
- WTG-09 had its generator brushes replaced under work order WO-26-0436 after alarm A3210 from 16/07.5
- The shortest measured brush on WTG-09 was B3 at 16 mm, below the 18 mm threshold in WI-GEN-014.5
- A complete LWS-P-51207 set was replaced on WTG-09, and the brush-holder screws were tightened to 12 N·m.5
- WTG-09 run-in was set at 50 % power for 8 hours, until 20:00 that evening.5
- WTG-07 had a maximum oil temperature of 66 °C that day, no alarm, and still had high vibration while awaiting the bearing.5
- WTG-04 had a ground-based visual inspection of blade B, with nothing new reported.5
- WTG-12 had its anti-pollution kit restocked.5
Handover action for next team
The next team is to verify the end of WTG-09 run-in at 20:00 and return it to 100 % power.6 The note repeats that it is fictional and not for operational use.6
Figures
No figures were extracted from this document.
Related
- Assets: Quellmoor Ridge Wind Farm, WTG-04, WTG-07, WTG-09, WTG-12
- Components: generator, generator brushes, rotor blade
- Spare part: LWS-P-51207
- Alarm code: A3210 Generator brush wear limit reached
- Procedure: WI-GEN-014 Generator brush replacement
- Topics: Gearbox temperature, vibration and oil analysis, Generator brushes and electrical systems
Sources
Footnotes
-
Shift Handover Note - Day Shift - 18/07/2026 — lines 1–4 · ✓ quote verified ↩
-
Shift Handover Note - Day Shift - 18/07/2026 — lines 6–12 · ✓ quote verified ↩ ↩2 ↩3 ↩4 ↩5 ↩6 ↩7
-
Shift Handover Note - Day Shift - 18/07/2026 — lines 14–15 · ✓ quote verified ↩
-
Shift Handover Note - Day Shift - 18/07/2026 — lines 1–4 · paraphrase ↩ ↩2
-
Shift Handover Note - Day Shift - 18/07/2026 — lines 6–12 · paraphrase ↩ ↩2 ↩3 ↩4 ↩5 ↩6 ↩7
-
Shift Handover Note - Day Shift - 18/07/2026 — lines 14–15 · paraphrase ↩ ↩2
Provenance badges✓ quote verified the quoted words were found verbatim in the source textparaphrase reworded from the source text; numbers checked, no verbatim quote