This shift handover note records the day-to-night status at Quellmoor Ridge Wind Farm on 2026-07-15. It covers curtailments, turbine observations, completed and postponed work, and actions for the next shift.

Key facts

  • The document is marked fictional and not for operational use.1
  • The handover is for 2026-07-15, from day shift to night shift.2
  • Callum Rydings, Lead Wind Technician, wrote the handover note.3
  • The site covered by the handover is Quellmoor Ridge Wind Farm.4
  • Grid curtailment was on day 2 of 3 under CPL-CI-2026-018; park export was limited to 20 MW from 08:00 to 18:00, and all turbines returned to normal at 18:00.5
  • WTG-03, WTG-04 and WTG-05 are expected to stop from 22:00 if wind remains low due to bat curtailment, and this should not be reset.5
  • WTG-07 still has HSS bearing vibration around 5.3 mm/s; oil temperature has been normal since the fan motor replacement, and WO-26-0412 is waiting for the bearing.5
  • On WTG-04, the 2026-07-02 drone check of blade B found the crack unchanged at 0.9 m.5
  • The WTG-05 daily checklist CHK-05 was completed yesterday with all items OK.6
  • Rescue kit inspections were performed on WTG-01 to WTG-04 under MP-HSE-01.6
  • Radiator cleaning MP-GBX-07 on WTG-03 was postponed to next week.6
  • The next shift should watch WTG-07 oil temperature in the afternoon.7
  • The spill kit of WTG-12 needs a refill, identified with AWI-20915.7
  • The document repeats the fictional, non-operational-use marking at the end.8

Contents

The note is marked fictional and not for operational use.9

It is titled as a shift handover for 2026-07-15 from day shift to night shift.10

It was written by Callum Rydings, Lead Wind Technician.11

The site is Quellmoor Ridge Wind Farm.12

Status

  • Grid curtailment was on day 2 of 3 under CPL-CI-2026-018; park export was limited to 20 MW from 08:00 to 18:00, and all turbines were back to normal at 18:00.13
  • WTG-03, WTG-04 and WTG-05 will stop from 22:00 if wind remains low due to bat curtailment, and this condition is normal and should not be reset.13
  • WTG-07 still had HSS bearing vibration around 5.3 mm/s; oil temperature had been normal since the fan motor replacement, and WO-26-0412 was waiting for the bearing.13
  • WTG-04 had a drone check of blade B on 2026-07-02, with the crack unchanged at 0.9 m.13

Work done today

  • The WTG-05 daily checklist CHK-05 was completed yesterday with all items OK.14
  • Rescue kit inspections were completed on WTG-01 to WTG-04 under MP-HSE-01.14
  • Radiator cleaning MP-GBX-07 on WTG-03 was postponed to next week.14

For the next shift

  • The next shift should watch WTG-07 oil temperature in the afternoon.15
  • The spill kit of WTG-12 needs a refill using or relating to AWI-20915.15

The note is again marked fictional and not for operational use.16

Figures

No figures were extracted from this document.

Sources

Footnotes

  1. Shift handover - 2026-07-15 (day shift to night shift) — line 1 · ✓ quote verified ↩

  2. Shift handover - 2026-07-15 (day shift to night shift) — line 3 · ✓ quote verified ↩

  3. Shift handover - 2026-07-15 (day shift to night shift) — line 5 · ✓ quote verified ↩

  4. Shift handover - 2026-07-15 (day shift to night shift) — line 7 · ✓ quote verified ↩

  5. Shift handover - 2026-07-15 (day shift to night shift) — lines 11–14 · ✓ quote verified ↩ ↩2 ↩3 ↩4

  6. Shift handover - 2026-07-15 (day shift to night shift) — lines 18–20 · ✓ quote verified ↩ ↩2 ↩3

  7. Shift handover - 2026-07-15 (day shift to night shift) — lines 24–25 · ✓ quote verified ↩ ↩2

  8. Shift handover - 2026-07-15 (day shift to night shift) — line 27 · ✓ quote verified ↩

  9. Shift handover - 2026-07-15 (day shift to night shift) — line 1 · paraphrase ↩

  10. Shift handover - 2026-07-15 (day shift to night shift) — line 3 · paraphrase ↩

  11. Shift handover - 2026-07-15 (day shift to night shift) — line 5 · paraphrase ↩

  12. Shift handover - 2026-07-15 (day shift to night shift) — line 7 · paraphrase ↩

  13. Shift handover - 2026-07-15 (day shift to night shift) — lines 11–14 · paraphrase ↩ ↩2 ↩3 ↩4

  14. Shift handover - 2026-07-15 (day shift to night shift) — lines 18–20 · paraphrase ↩ ↩2 ↩3

  15. Shift handover - 2026-07-15 (day shift to night shift) — lines 24–25 · paraphrase ↩ ↩2

  16. Shift handover - 2026-07-15 (day shift to night shift) — line 27 · paraphrase ↩

Provenance badges✓ quote verified the quoted words were found verbatim in the source textparaphrase reworded from the source text; numbers checked, no verbatim quote